|
Article
51 – Semiconductor Fabrication Facilities |
| 5101.10.4
Continuous gas-detection systems |
5101.10.4.1
General. A continuous gas-detection system shall be provided for HPM gases
when the physiological warning properties of the gas are at a higher level than
the accepted permissible exposure limit (PEL) for the gas and for flammable gases
in accordance with Section 5101.10.4.
|
| 5101.10.4.2
Where required |
| 5101.10.4.2.1
Fabrication areas. A continuous gas-detection system shall be provided for
fabrication areas at locations in the fabrication area where gas is used or stored. |
| 5101.10.4.2.2
HPM rooms. A continuous gas-detection system shall be provided in HPM rooms
when gas is used in the room. |
| 5101.10.4.2.3
Gas cabinets, exhausted enclosures and gas rooms. A continuous gas- detection
system shall be provided in gas cabinets, exhausted enclosures and gas rooms. |
| 5101.10.4.2.4
Corridors. When gases are transported in piping placed within the space defined
by the walls of a corridor and the floor or roof above the corridor, a continuous
gas-detection system shall be provided where piping is located and in the corridor. |
| EXCEPTION:
A continuous gas-detection system is not required for occasional transverse crossings
of the corridors by supply piping which is enclosed in a ferrous pipe or tube
for the width of the corridor. |
| 5101.10.4.3
Gas-detection system operation |
| 5101.10.4.3.1
Monitoring. The continuous
gas-detection system shall be capable of monitoring the location where gas detection
is required at or below the permissible exposure limit (PEL) or ceiling limit
of the gas for which detection is provided. For flammable gases, the monitoring
detection threshold level shall be vapor concentrations in excess of 20 percent
of the lower explosive limit (LEL). See also Section 8003.3.1.6. |
| 5101.10.4.3.2
Alarms. The gas-detection system
shall initiate a local alarm and transmit a signal to the emergency control station
when a short-term hazard condition is detected. The alarm shall be both visual
and audible and shall provide warning both inside and outside the area where the
gas is detected. The audible alarm shall be distinct from all other alarms. |
| 5101.10.4.3.3
Shut off of gas supply. The
gas-detection system shall automatically close the shutoff valve at the source
on gas supply piping and tubing related to the system being monitored for which
gas is detected when a short-term hazard condition is detected. Automatic closure
of shutoff valves shall be in accordance with the following: |
| EXCEPTION:
When the gas-detection sampling
point initiating the gas-detection system alarm is at a use location or within
a gas valve enclosure of a branch line downstream of a piping distribution manifold,
the shutoff valve in the gas valve enclosure for the branch line located in the
piping distribution manifold enclosure shall automatically close. |
| 1. | When
the gas-detection sampling point initiating the gas detection system alarm is
within a gas cabinet or exhausted enclosure, the shutoff valve in the gas cabinet
or exhausted enclosure for the specific gas detected shall automatically close. |
| 2. | When
the gas detection sampling point initiating the gas detection system alarm is
within a room and compressed gas containers are not in gas cabinets or exhausted
enclosures, the shutoff valves on all gas lines for the specific gas detected
shall automatically close. |
| 3. | When
the gas-detection sampling point initiating the gas detection system alarm is
within a piping distribution manifold enclosure, the shutoff valve for the compressed
gas container of specific gas detected supplying the manifold shall automatically
close. |